title: COSEL Power Supply, Noise Filter 2025 Product Catalog

page
1104/1330

This page is the summary of page 1104 of the ebook "COSEL Power Supply, Noise Filter 2025 Product Catalog."

You can click "Open This Page" or "Open 1st Page" button, and open the ebook.

Summary

COSEL Power Supply, Noise Filter 2025 Product Catalog

AC-DC Power Supplies Medical Type GHA300F, GHA500F Instruction Manual6.3 External capacitor on the output side!When the load currnet changes rapidly, for output stability improvement,we recommend that you connect the capacitor to theoutput terminal.Tabel 6.5 External capacity on the output recommended capacity [μF]Output Voltage[V]Recommendedcapacity[μF]GHA300F-12GHA500F-1210.8[Vo[13.22,200 to 22,000GHA500F-1513.5[Vo[16.52,200 to 10,000GHA300F-24GHA500F-2421.6[Vo[26.43,300 to 8,800GHA500F-3027.0[Vo[31.53,300 to 8,800GHA300F-4843.2[Vo<51.00 to 1,000GHA500F-4851.0[Vo[52.80 to 120GHA500F-5652.0[Vo[56.00 to 120Remarks:When load current changes rapidly, some specifications may notmeet the spec.Please mount power supply after enough evaluation and complywith recommended amount of capacitor. If you exceed the ratedamount of capacitor, output for power supply may be stopped orpower supply may be unsteable.6.4 Others!High voltage exist in the power supply for a few minutes afterinput voltage is stopped. Please pay attention to this during themaintence.!Notes for mounting1All Mounting holes should be tight and secured.2 Power supply should be mounted parallel to the mounting surface.3Avoid applying mechanical stress or shock to the power supply.!When power supply is energized or immidately after power supplystops working, power supply is still very hot, so please handle itwith care.GHA-23